Feldbus-baugruppe 2113 interbus, Show/hide bookmarks – Lenze EMF2113IB User Manual

Page 59

Advertising
background image

Data transfer

Process data signals of Lenze controllers

7

Feldbus-Baugruppe 2113 INTERBUS

7.6
7.6.2

L

7.6-8

EDSIBS-1.0-06/2003

Device status word AIF-STAT for 82XX (Lenze code C0150, index 5F69

hex

)

Bit

820X

821x, 822x

0

Actual parameter set

0 = Parameter set 1 or 3 active
1 = Parameter set 2 or 4 active

Actual parameter set

0 = Parameter set 1 or 3 active
1 = Parameter set 2 or 4 active

1

IMP (pulse inhibit)

0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited

IMP (pulse inhibit)

0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited

2

I

max

(current limit reached)

0 = Current limit not reached
1 = Current limit reached

I

max

(current limit reached)

0 = Current limit not reached
1 = Current limit reached

3

not assigned

f

d

= f

dset

0 = f

d

≠ f

dset

1 = f

d

= f

dset

4

f

d

= f

dset

0 = f

d

≠ f

dset

1 = f

d

= f

dset

RFG on = RFG off

0 = RFG on

≠ RFG off

1 = RFG on = RFG out

5

Qmin (f

d

≤ f

dQmin

)

0 = Qmin not active
1 = Qmin active

Qmin (f

d

≤ f

dQmin

)

0 = Qmin not active
1 = Qmin active

6

f

d

+ 0 (act. frequency = 0)

0 = f

d

≠ 0

1 = f

d

+ 0

f

d

+ 0 (act. frequency = 0)

0 = f

d

≠ 0

1 = f

d

+ 0

7

Ctrl. inhibit (controller inhibit)

0 = Controller not inhibited
1 = Controller inhibited

Ctrl. inhibit (controller inhibit)

0 = Controller not inhibited
1 = Controller inhibited

8...11 Controller status

0 = Unit initialisation
8 = Error active

Controller status

0 = Controller initialization
2 = Switch on inhibit

3 = Operation inhibited

4 = Flying-restart circuit active
5 = DC brake active

6 = Operation enabled

7 = Message active
8 = Error active

12

Overtemperature warning

0 = No warning
1 = Warning

Overtemperature warning

0 = No warning
1 = Warning

13

V

Gmax

(DC-bus overvoltage)

0 = No overvoltage
1 = Overvoltage

V

Gmax

(DC-bus overvoltage)

0 = No overvoltage
1 = Overvoltage

14

Direction of rotation

0 = CW rotation
1 = CCW rotation

Direction of rotation

0 = CW rotation
1 = CCW rotation

15

Ready for operation

0 = Not ready for operation
1 = Ready for operation

Ready for operation

0 = Not ready for operation
1 = Ready for operation

16 bits

16 bits

.B15

.B12

.B0
.B1
.B2
.B3
.B4

.B8
.B9
.B10
.B11

.B13
.B14

.B5
.B6
.B7

IMP

fd=fdset / RFG

Qmin

Imax

- / fd=fdset

PAR

fd>0

ctrl. inhibit

Vgmax

R/L

RDY

T ü

AIF

C0050

STAT

B11 B10 B9 B8

0
0

1...

...

0
1

1...

...

0
0

0...

...

0
0

0...

...

0
2

3...

...

2141LON012_en

Fig. 7.6-1

Read access to status word and actual frequency in 82XX (fixed assignment)