Commissioning

Possible settings with the front switch

7

Feldbus-Baugruppe 2113 INTERBUS

7.5
7.5.2

L

7.5-2

EDSIBS-1.0-06/2003

7.5.2

Possible settings with the front switch

)

)

)

)

Note!

Switches S1 ... S7

l

All in OFF position:
The configurations set for the codes L-1910, L-1911 and
L-1912 get active with switching on.

l

One or several switches in ON position:
All switch positions are valid!
The following must be set:
– Number of process data words (PD),
– Number of parameter data words (PCP) and
– Device control AIF-CTRL / DRIVECOM control

The Lenze setting of the switches (S1 - S8) is OFF .

Switch off the voltage supply of the fieldbus module and
afterwards on again, in order to activate changed settings.

As a maximum the data word sum (PD + PCP) is to amount to 10
words.

Please note that only the switch combinations listed in the
following tables represent defined states. If the settings are
unacceptable, the yellow bus LED at the front of the fieldbus
module will start blinking (8kHz).

ON

OFF

OPEN

1 2 3 4

5 6 7 8

Length

PD

2113IBU005

PD

S1

S2

S3

S4

Maximum number of
parameter data words

(PCP)

1

OFF

OFF

OFF

ON

2

OFF

OFF

ON

OFF

3

OFF

OFF

ON

ON

4

4

OFF

ON

OFF

OFF

4

5

OFF

ON

OFF

ON

6

OFF

ON

ON

OFF

7

OFF

ON

ON

ON

2

8

ON

OFF

OFF

OFF

2

9

ON

OFF

OFF

ON

1

10

ON

OFF

ON

OFF

0

)

)

)

)

Note!

Impermissible settings are indicated by the yellow bus LED
(communication).

(

¶ 7.4-1)

.

Display of the current switch position S1 ... S4 for number of
process data words (PD) is possible because of code L-C1915.

Setting number of process data
words (PD)

30

Show/Hide Bookmarks