Feldbus-baugruppe 2113 interbus, Data transfer drivecom profile parameters – Lenze EMF2113IB User Manual

Page 85

Advertising
background image

Data transfer

DRIVECOM profile parameters

7

Feldbus-Baugruppe 2113 INTERBUS

7.6
7.6.7

L

7.6-34

EDSIBS-1.0-06/2003

7.6.7.2

Monitoring parameters

If the transmission of the process data is inactive for longer than the set monitoring
time (PCD watchdog), the action set in the parameter ” process-data monitoring
selection code” (6004

hex

) will be activated.

Parameter name (Index)

Subindex

Data structure

Data type

Value range

Process data monitoring time
(6003

hex

)

0

S

OS-1
OS: Octet
string,

length: 4

0 - 65535
(Lenze setting:

65535,

monitoring is switched off)

The parameter determines the reaction of the controller after the process data
monitoring time is over (6003

hex

).

Parameter name (Index)

Subindex

Data structure

Data type

Value range

Process data monitoring selection
code (6004

hex

)

0

S

I16

0 (Lenze setting),

0 = No action
2:

Unit control command
„Inhibit voltage“ (controller

inhibit with latching in the

status ”SWITCH ON INHIBIT“)
3:

Unit control command

”Quick stop“ (quick stop
(QSP) with latching in the

status ”SWITCH ON

INHIBIT“).

Process data monitoring time
(6003

hex

)

Process data monitoring
selection code (6004

hex

)

Show/Hide Bookmarks