Installation

Electrical installation

7

Feldbus-Baugruppe 2113 INTERBUS

7.4
7.4.3

L

7.4-4

EDSIBS-1.0-06/2003

Pos.

Element

Explanation

1

INTERBUS master with
interface module

The bus system is a master-slave system, i.e. an INTERBUS master is connected
to several field devices (slaves).

2

INTERBUS loop bus
terminal

The bus terminal connects a long distance bus to a peripheral bus.

3

Remote bus
Fig. 5.4-2 Pos. 3

The following connections are possible with remote buses:

Connections between INTERBUS master interface module and first bus
terminal or first 2113 fieldbus module.

Connection between bus terminal and 2113 fieldbus module

Connection between two 2113 fieldbus modules

3.1

Long distance bus module Bus participant in the long distance bus; e.g. Lenze controller with INTERBUS

module (slave). Networking does not require bus terminals.

3.2

Remote bus cable

Connects the INTERBUS master interface module with the bus terminal and/or
the long distance bus modules.

4

INTERBUS loop,
peripheral bus
Fig. 5.4-2 Pos. 4

Connection in a peripheral-bus station
A peripheral-bus station consists of:

a bus terminal (Fig. 5.4-2 pos. 2)

up to eight peripheral bus modules (Fig. 5.4-2 pos. 3)

4.1

INTERBUS loop module

Bus participant in the INTERBUS loop; e.g. Lenze controller with INTERBUS loop
module 2112

4.2

INTERBUS loop cable

Connection within the loop

Features:
Communication medium

RS485

Network topology

Ring

Maximum number of
controllers

Dependent on INTERBUS master (e.g. Phoenix Contact G4-Master).
For the following data, always the smaller value applies dependent on the fact, whether
PCP communication is available or not:

With PCP communication:

62

or

Without PCP communication:

256/number PD

Baud rate / cable length

Baud rate

Maximum cable length between
neighbouring participants

500 kBit/s

400 m

2 MBit/s

150 m

Specification of INTERBUS remote bus cable

26

Cable type

Yard goods:
IBS RBC Meter-T, order No. 28 06 28 6 (Fa. Phoenix Contact)

Number of conductors

3 x 2, paired with common shielding

Conductor cross-section

> 0.2 mm

2

DC cable resistance

< 96

Ω/km

Impedance, characteristic

120

Ω ± 20 % (f = 64 kHz)

100

Ω ± 15 Ω (f > 1 MHz)

Capacitance per unit length

< 60 nF/km (f = 800 Hz)

If necessary, supply the 2113 fieldbus module with a separate supply voltage 24
V DC via the two-pole plug connector

±10 %.

Plug connector

Name

Explanation

+

Vcc24

External supply 24 V DC ± 10 %, 120 mA

-

GND24

Reference potential for external voltage supply

Use a separate power supply unit in each control cabinet.

Controller

External voltage supply

820X

Always required

821X / 822X / 824X and
93XX

Only necessary if the mains which supply the corresponding controllers is to be switched
off but the communication must not be interrupted.

8200 vector

See information in “internal DC voltage supply”

External DC voltage supply

27