EMF2179IB communication module (DeviceNet)

Installation

Electrical installation

5

5.4

5.4.3

5.4-4

EDSDEN EN 02/2006

DeviceNet

n

120R

120R

2175DEN010

n

Number of nodes

120R

Terminating resistor

A DeviceNet line can have max. 63 participants. The participants are
ƒ the connected basic devices
ƒ the DeviceNet master (scanner)
ƒ all other components which take part in the communication.
Inthere, the basic devices withplugged-on communicationmodules and the

DeviceNet master can communicate.
A PC with installed software (e.g. RSNetWorx) is used to integrate the

communication modules.

Note!

Please observe that

ƒ

the shield on the voltage supply is to be connected together

with the ”V-” connection to GND once. For this, use the centre

point of the DeviceNet line, if possible.

ƒ

for each participant the shield of the DeviceNet cable is only

connected to the ”shield” connection of the plug connector.

ƒ

the DeviceNet line is terminated by 120-Ohm resistors at both

ends.