EMF2179IB communication module (DeviceNet)
Lenze codes and DeviceNet objects
Implemented DeviceNet objects
5
5.7
5.7.2
5.7-6
EDSDEN EN 02/2006
Instance 0:
Attribute
Service(s)
Description
Data type
Value
1
GET
Revision
UINT
0002
hex
Instance 1:
Attribute
Service(s)
Description
Data type
Value
1
GET
MAC ID
USINT
0 - 63
2
GET
Baud rate
USINT
0 - 2
3
GET / SET
BOI
BOOL
0/1
4
GET
Bus-off counter USINT
0 - 255
5
GET
Allocation
information
Struct of
Allocation
choice byte
BYTE
0 – 63
Master’s MAC ID USINT
0 – 63
Services:
Service code Name
Description
0E
hex
Get_Attribute_Single
Reading of an attribute
10
hex
Set_Attribute_Single
Writing of an attribute
4B
hex
Allocate_Master/Slave_Connection_Set Demands the application of
“Predefined Master/Slave Connection
Set”
4C
hex
Release_Group_2_Identifier_Set
Connections via “Predefined
Master/Slave Connection Set” are
deleted
DeviceNet Class (03