EMF2179IB communication module (DeviceNet)
Commissioning
Possible settings via DIP switch
5
5.5
5.5.1
5.5-3
EDSDEN EN 02/2006
OPEN
ON
OFF
Address Bd
1 2
4
3
5 6 7 8 9 10
Fig. 5.5-2
Address assignment via DIP switch
The address (decimal number) is calculated by inserting the positions of
switches S1 to S6 (’0’ = OFF and ’1’ = ON) into the following equation.
Address
dec
= S6 · 2
0
+ S5 · 2
1
+ S4 · 2
2
+ S3 · 2
3
+ S2 · 2
4
+ S1 · 2
5
The equation can also be used to calculate the valency of a switch. The sum
of valencies results in the node address to be set:
Switch
Valency
Example
Switch position
Node address
S1
32
ON
32 + 16+ 8 = 56
S2
16
ON
S3
8
ON
S4
4
OFF
S5
2
OFF
S6
1
OFF
Setting of the device address