EMF2179IB communication module (DeviceNet)

Commissioning

Preparing the basic device for communication

5

5.5

5.5.4

5.5-7

EDSDEN EN 02/2006

5.5.4

Preparing the basic device for communication

Note!

During operation, the change of a communication module to

another basic device can lead to undefined operating states.

1. Set the Lenze parameter operating mode (C0001) to ”3” to enable the

controller via the communication module. This can be made using the

keypad or directly via DeviceNet.
Lenze codes in the controller and communication module can be read and

written via the vendor-specific class 110.

ƒ Example: write C0001 = 3

– Class: 0x6E
– Instance: 0x1
– Attribute: 0x1
– Service code: set single attribute
– Data sent: 0x7530 (30 000

dec

)

For further examples, see ( 5.7-17).

2. Terminal 28 (controller enable) is always active and must be set to

HIGH level during DeviceNet operation (see Operating Instructions for

the controller).
– Otherwise, the controller cannot be enabled.
– With 821X, 8200vector and 822X, the QSP (quick stop) function is

always active. If QSP is assigned to an input terminal (Lenze setting:

not assigned), this terminal must be at HIGH level during DeviceNet

operation (see Operating Instructions for the controller).

82XX / 8200 vector frequency