Specific features for parameterising the controller
For the 8200 inverter series, the following specific features apply:
Danger!
Parameter setting (codes except C046, C0135) can only be
effected if the controller is inhibited. Though parameters are
accepted if the controller is enabled, they are discarded
afterwards.
After parameterisation of a value, the controller may not be
activated via “Explicit Message” for approx. 50 ms, as otherwise
these commands are ignored!
After completion of the entire paramterisation process, a period
of approx. 70 ms can pass until controller enable (terminal, C040,
C0135) is accepted.
The TRIP reset function (reset of a fault) is carried out by setting
controller inhibit and then controller enable via C040 or C0135.
8200 drive controller