Emf2179ib communication module (devicenet) – Lenze EMF2179IB User Manual

Page 78

Advertising
background image

EMF2179IB communication module (DeviceNet)

Lenze codes and DeviceNet objects

Specific features for parameterising the controller

5

5.7

5.7.3

5.7-19

EDSDEN EN 02/2006

5.7.3

Specific features for parameterising the controller

For the 8200 inverter series, the following specific features apply:

Danger!

Parameter setting (codes except C046, C0135) can only be

effected if the controller is inhibited. Though parameters are

accepted if the controller is enabled, they are discarded

afterwards.

After parameterisation of a value, the controller may not be

activated via “Explicit Message” for approx. 50 ms, as otherwise

these commands are ignored!
After completion of the entire paramterisation process, a period

of approx. 70 ms can pass until controller enable (terminal, C040,

C0135) is accepted.
The TRIP reset function (reset of a fault) is carried out by setting

controller inhibit and then controller enable via C040 or C0135.

8200 drive controller