5 status display, Status display, Emf2179ib communication module (devicenet) – Lenze EMF2179IB User Manual

Page 58

Advertising
background image

EMF2179IB communication module (DeviceNet)

Commissioning

Status display

5

5.5

5.5.5

5.5-11

EDSDEN EN 02/2006

5.5.5

Status display

2179DeN001B

Pos.

Colour Condition

Description

Green Blinking

Communication module is supplied with voltage but is not

connected to the controller (controller is switched off,

initialising, or not available).

On

Communication module is supplied with voltage and is

connected to the controller.

Off

z

No communication with the communication module

z

Communication module is not supplied with voltage

Green Blinking

Dup_Mac_ID testing. Still no connection to the master.

Green On

DeviceNet connection built up.

Red

Blinking

No communication because time limit exceeded

Red

On

Internal fault of the communication module

Operating status of the basic device (see instructions for the basic device)