EMF2179IB communication module (DeviceNet)

Commissioning

Possible settings via DIP switch

5

5.5

5.5.1

5.5-4

EDSDEN EN 02/2006

Note!

The baud rate must be the same for all devices and the scanner.

OPEN

ON

OFF

Address Bd

1 2

4

3

5 6 7 8 9 10

Fig. 5.5-3

Baud rate setting

Baud rate

S7

S8

125 kbits/s

OFF

OFF

250 kbits/s

OFF

ON

500 kbits/s

ON

OFF

Baud rate setting