EMF2179IB communication module (DeviceNet)
Commissioning
Possible settings via DIP switch
5
5.5
5.5.1
5.5-4
EDSDEN EN 02/2006
Note!
The baud rate must be the same for all devices and the scanner.
OPEN
ON
OFF
Address Bd
1 2
4
3
5 6 7 8 9 10
Fig. 5.5-3
Baud rate setting
Baud rate
S7
S8
125 kbits/s
OFF
OFF
250 kbits/s
OFF
ON
500 kbits/s
ON
OFF
Baud rate setting