Emf2179ib communication module (devicenet) – Lenze EMF2179IB User Manual

Page 57

Advertising
background image

EMF2179IB communication module (DeviceNet)

Commissioning

Preparing the basic device for communication

5

5.5

5.5.4

5.5-10

EDSDEN EN 02/2006

Note!

In some cases the controller should not restart after a fault (e.g.

after a short mains failure).

ƒ

The drive can be inhibited by setting C0142 = 0 if

the corresponding controller sets a fault ”LU message” and

the fault is active for more than 0.5 seconds.

Parameter function:

ƒ

C0142 = 0

The controller remains inhibited even after the fault has

been eliminated and

the drive restarts in a controlled mode: LOW-HIGH transition

at terminal 28 (CINH)

ƒ

C0142 = 1

An uncontrolled restart of the controller is possible.

Lenze codes in the basic device and communication module can

be read and written via the vendor-specific class 110. An

example is included in the appendix of the DeviceNet Manual

(Class Instance Editor).

Protection against

uncontrolled restart