Voltage supply

For DeviceNet always an external voltage supply is used.

Designation

Explanation

V+

External supply (exceeds the selection of the DeviceNet specification)

V = 24 V DC (21.6 V - 0 % ... 26.4 V + 0 %)

I = 100 mA

V-

Reference potential for external voltage supply

If the distance between the DeviceNet participants is larger than normal,

you can use several voltage supplies.

Controller

External voltage supply

820X

Always required

821X, 822X, 824X,

93XX and ECS

Only necessary, if the mains supplying the corresponding controllers is

to be switched off but the communication must not be interrupted.

8200 vector

See “Internal DC voltage supply”

Note!

The internal voltage supply option is available for basic devices

with extended AIF interface opening (8200 vector front). The

area marked in grey in the graphic representation indicates the

jumper position.

ƒ

In the delivery status of the frequency inverters, these are not

supplied internally.

ƒ

For internal voltage supply put the jumper on the position

indicated below.

Lenze setting

(only external voltage supply)

Internal voltage supply

External voltage supply