4 communication connection, Communication connection, Emf2179ib communication module (devicenet) – Lenze EMF2179IB User Manual
Page 44: Installation communication connection
Advertising
EMF2179IB communication module (DeviceNet)
Installation
Communication connection
5
5.4
5.4.4
5.4-9
EDSDEN EN 02/2006
5.4.4
Communication connection
Use the 5-pole plug connector with double screw connection to connect the
communication module to the bus.
The assignment of the plug connector and the cable colour used according
to the DeviceNet Specification are listed in the table.
qÜáÅâ
120R
V-
CAN_L SHLD
V+
CAN_H
qÜáå
Designation Cable colour
Explanation
V-
Black
Reference for external voltage supply
CAN_L
Blue
Data cable / input for terminating resistor of 120 Ohm
SHLD
Shield
CAN_H
White
Data cable / input for terminating resistor of 120 Ohm
V+
Red
External voltage supply ; see 5.4-11
V
cc
V
cc
V+
CAN-HIGH
Shield
CAN-LOW
V-
7
6
2
8
5
3
1
4
2175DeN007
Internal wiring of the bus
terminals