Emf2179ib communication module (devicenet) – Lenze EMF2179IB User Manual
Page 72
EMF2179IB communication module (DeviceNet)
Lenze codes and DeviceNet objects
Implemented DeviceNet objects
5
5.7
5.7.2
5.7-13
EDSDEN EN 02/2006
Instance 0:
Attribute
Service(s)
Description
Data type
Value
1
GET
Revision
UINT
0001
hex
Instance 1:
Attribute
Service(s)
Description
Data type
Value
1
GET / SET
Response to
IdleMode
UINT
0 = no response
1 = CINH
2= QSP
2
GET / SET
Response to
communicatio
n errors
UINT
0 = no response
1 = CINH
2= QSP
3
GET / SET
Response to
BusOff
UINT
0 = no response
1 = CINH
2= QSP
Services:
Service code
Name
Description
0E
hex
Get_Attribute_Single
Reading of an attribute
10
hex
Set_Attribute_Single
Writing of an attribute
Note!
The parameters of 65
hex
are described in the EDS file and
therefore can be directly set in the feature dialog of the
DeviceNet nodes under ”Parameters” via the »RSNetWorx«
Rockwell software.
Manufacturer-specific class
101 (65
hex
):
response to IdleMode,
response to communication
errors,
response to BusOff