Emf2179ib communication module (devicenet) – Lenze EMF2179IB User Manual

Page 72

Advertising
background image

EMF2179IB communication module (DeviceNet)

Lenze codes and DeviceNet objects

Implemented DeviceNet objects

5

5.7

5.7.2

5.7-13

EDSDEN EN 02/2006

Instance 0:

Attribute

Service(s)

Description

Data type

Value

1

GET

Revision

UINT

0001

hex

Instance 1:

Attribute

Service(s)

Description

Data type

Value

1

GET / SET

Response to

IdleMode

UINT

0 = no response

1 = CINH

2= QSP

2

GET / SET

Response to

communicatio

n errors

UINT

0 = no response

1 = CINH

2= QSP

3

GET / SET

Response to

BusOff

UINT

0 = no response

1 = CINH

2= QSP

Services:

Service code

Name

Description

0E

hex

Get_Attribute_Single

Reading of an attribute

10

hex

Set_Attribute_Single

Writing of an attribute

Note!

The parameters of 65

hex

are described in the EDS file and

therefore can be directly set in the feature dialog of the

DeviceNet nodes under ”Parameters” via the »RSNetWorx«

Rockwell software.

Manufacturer-specific class

101 (65

hex

):

response to IdleMode,

response to communication

errors,

response to BusOff

Advertising