Emf2179ib communication module (devicenet) – Lenze EMF2179IB User Manual

Page 56

Advertising
background image

EMF2179IB communication module (DeviceNet)

Commissioning

Preparing the basic device for communication

5

5.5

5.5.4

5.5-9

EDSDEN EN 02/2006

1. For drive control via DeviceNet, use the EMZ9371BC keypad or the

DeviceNet and set the Lenze parameter signal configuration (C0005) to

a value implementing communication via the AIF interface:

ƒ Variant ”Speed & Torque”: C0005 = 1013

(speed control via AIF interface)

ƒ Variant ”Posi & Shaft”: C4010 = 2

(automation interface AIF X1)

ƒ Example: write C0005 = 1013

– Class: 0x6E
– Instance: 0x5
– Attribute: 1
– Service code: set single attribute
– Data sent: 0x9A9250 (10 130 000

dec

)

2. Terminal SI1 (controller enable) and SI2 (IMP = pulse inhibit) are always

active and must be set to HIGH level during operation. Otherwise, the

controller is inhibited.

Note!

The controller must always be externally supplied with 24 V DC.

3. The controller can now accept DeviceNet control and parameterisation

data.

4. Select speed / position setpoint
ƒ Variant ”Speed & Torque”: select the speed setpoint with a value

unequal 0.

ƒ Variant ”Posi & Shaft”: select the position setpoint with a value

unequal 0.
Prior to this, the position profiles must be parameterised according to the

Operating Instructions for the controller.

ECS servo system, variants

”Speed & Torque” and

”Posi & Shaft”