EMF2179IB communication module (DeviceNet)

Troubleshooting

5

5.8

5.8-1

EDSDEN EN 02/2006

5.8

Troubleshooting

Possible causes

Diagnostics

Remedy

Is the controller switched on? One of the operating status

LEDs of the basic device must

be on.

Supply controller with voltage.

Is the communication module

supplied with voltage?

The LED ”Connection status to

the basic device” must be lit or

blinking green.

Check the external voltage

supply.

The measured voltage value at

the terminals for external

voltage supply of the

communication module must

be in the range of 24 V ± 10 %.
The communication module

has not yet been initialised

with the controller.

Possibility 1: controller not

switched on

Possibility 2: check the

connection to the controller

Does the controller receive

telegrams?

The LED ”Connection status to

the bus” at the

communication module must

be blinking green when

communicating with the

master computer.

Check your wiring

(see  5.4-1).

Check whether your master

computer sends telegrams.

Check the data assignment in

the scan list (I/0 mapping).
Is the available device address

already assigned?

Check the setting of the other

nodes on the DeviceNet.

No communication with the

controller.