3.1.1 Safety Standards 
 
MSR300 Series Modules conform to the Essential Health & Safety Requirements 
(EHSR's) of the European Machinery Directive (98/37/EC), the relevant requirements of 
the Low Voltage Directive (73/23/EEC as amended by 93/68 EEC) and the essential 
protection requirements of the EMC Directive (89/336/EEC as amended by 92/31 EEC). 
The MSR310P also conforms to EN 292, EN 60204-1, EN61508, EN 954-1, and UL 508. 
 
 
3.1.1.1 EN 
954-1
 
This product conforms to Category 4 of EN954-1: Safety-Related Parts Of Control 
Systems. 
 
The main stipulations of this standard are: 
 
Safety-related parts of control systems conforming to Category 4 shall be designed so 
that: 
• A single fault in any of these safety-related parts does not lead to a loss of the
safety function.
• The single fault is detected at or before the next demand upon the safety functions,
e.g. immediately at switch on, at end of a machine operating cycle. If this detection 
is not possible, then an accumulation of faults shall not lead to a loss of the safety 
function. 
 
If the detection of certain faults is not possible, at least during the next check-up after the 
occurrence of the fault, for reasons of technology or circuit engineering, the occurrence of 
further faults shall be assumed. In this situation the accumulation of faults shall not lead 
to the loss of the safety function. 
 
Fault review may be stopped when the probability of occurrence of further faults is 
considered to be sufficiently low. In this case the number of faults in combination, which 
need to be taken into consideration, will depend upon the technology, structure and 
application but shall be sufficient to meet the detection criteria. 
 
 
3.1.1.2 IEC/EN 
61508
 
This product has been designed to conform to SIL 3 of IEC/EN 61508: Functional Safety 
of Electrical / Electronic / Programmable Electronic Safety-Related Systems, Parts 1-7, 
1998. 
 
IEC/EN 61508 relates to the functional safety of electrical, electronic, and programmable 
electronic safety-related systems. These are referred to as Safety Instrumented Systems 
(SIS). IEC/EN 61508 is an umbrella standard applicable to all industries. Safety Integrity 
Level (SIL) is a statistical representation of the reliability of the SIS. Four SIL levels are 
defined: SIL 1 through SIL 4. The higher the SIL number, the more reliable or effective