MSR300 Safety System Manual


Rockwell Automation

MSR300 Manual.doc

Pg 22 of 85

Y40, Y41, Y42

Reset configuration

S34

Start button

Y31 – Y33

Solid-state auxiliary outputs for groups 1, 2 and 3

Y10

+24V for reset circuit and feedback loops

Y11 – Y13

Feedback loop inputs for Groups 1, 2 and 3



4.1.2 LED Indicators

Function

Status LED

Group 1-2-3 LEDs

Power up / normal operation

Continuous on: green

---

Internal fault

Continuous on: red

---

Entering configuration mode

1 flash: red

---

Input switch fault or reset switch
closed during power up

2 flashes; red

---

Configuration change during
operation

3 flashes; red

---

Current configuration not as stored
on EEPROM

4 flashes; red

---

At least one muting lamp and one
reserve lamp defective

5 flashes; red

---

Invalid switch settings of input
modules

6 flashes; red

---

Invalid reset configuration (Y41,
Y42, S34 terminal jumpers)

7 flashes; red

---

Input terminal block not (or
improperly) plugged in

8 flashes; red

---

Group output active

---

Continuous on: green

Group ready

---

Blinking: green

At least one input corresponding to
the output group is faulty

---

Continuous on: red

A feedback (EDM) loop of the
output group is open, or no input is
assigned to the group

--- Off



LEDs "TxD1" and "TxD2" indicate RS232 data communication activity when flashing.