6.2

Recoverable Faults During Start-Up or Operation


Recoverable faults are also indicated by the "Status" LED, but by different flashing
patterns.

The various recoverable faults and their corresponding LED flashing patterns are
described below.
Note: Shut down power before corrective action (except Input switch fault). After
modification of configuration the set-up procedure as described in the next chapter is
required.

[In the LED Indication column, a number followed by "x" means that the LED flashes
(blinks) that many times, followed by a pause. The cycle repeats while the fault condition
exists.]

Fault Indication

Corrective

Action

Input switch fault (if switch
monitoring is enabled).

"Status" LED flashes 2 x.
LED of the faulty input
flashes, red.

Unlock the faulty input.

The reset pushbutton
(momentary switch) is
pressed while the system is
being powered up.

"Status" LED flashes 2 x.

Replace the reset switch.

Configuration changes
during operation.
(Terminals Y40, Y41, Y42,
S34).

"Status" LED flashes 3 x.

Check the jumpers at
terminals Y40, Y41, Y42,
S34.

The actual configuration
does not match what has
been previously stored in
EEPROM.

"Status" LED flashes 4 x.

Check the system
configuration. Reconfigure
as necessary, or have the
system read and store the
current configuration.

At least one muting lamp
and reserve lamp are
defective.

"Status" LED flashes 5 x.

Check and replace both
defective lamps.

Bus terminator plug of last
Input Module not (or
improperly) plugged in.

"Status" LED flashes 8 x.

Insert the bus terminator
plug.