MSR300 Safety System Manual


Rockwell Automation

MSR300 Manual.doc

Pg 36 of 85

4.2.3.9

Safety Gate and Light Curtain


Switch setting: 9

Without simultaneity monitoring of Input 1 and Input 2.

Input 1

Input 2

Solid-state auxiliary
output: Input 1

Solid-state auxiliary
output: Input 2

S11-S12: N/C
S11-S22: N/O

OSSD1-S42
OSSD2-S52

S32

S62










With simultaneity monitoring (3 second limit) of Input 1 and without simultaneity
monitoring of Input 2.

Input 1

Input 2

Solid-state auxiliary
output: Input 1

Solid-state auxiliary
output: Input 2

S21-S12: N/C
S21-S22: N/O

OSSD1-S42
OSSD2-S52

S32

S62

See respective wiring diagrams for safety door and light curtain (above).