4.1.3 Settings, Connections, Start-Up

Reset mode selection (reset switch connection and jumper settings):

Reset button has to be installed at a place where the dangerous area can
be visual monitored. Automatic reset is only allowed if the start of the
machine cannot lead to a hazard or a restart interlock must be
accomplished by other means of control (per EN 60204-1)


Reset behavior

Circuit

Group1 and 2: manual, monitored reset
Group3: automatic reset



Group 1 and 2: automatic reset
Group 3: manual, monitored reset




Groups1, 2 and 3: manual, monitored
reset



Groups 1, 2 and 3: automatic reset