7.2 Installation

7.2.1 Environmental Considerations

















MSR300 Series Modules must be installed inside protected control
panels / cabinets appropriate for the environmental conditions of the
industrial location. The protection class of the panel / cabinet should
preferably be IP 54 or higher.

The environmental protection ratings of the modules in accordance
with IEC/EN 60529 are:
Housing: IP 40
Terminals: IP 20

Operating ambient condition limits are:
Operating temperature: -5°C to +55°C (+23°F to 131°F)
Relative humidity (RH): 90% (max.)