Rockwell Automation 440R MSR300 Modular Safety Control System User Manual
Page 51
 
MSR300 Safety System Manual
 
Rockwell Automation 
MSR300 Manual.doc
Pg 51 of 85
6.3
Recoverable Configuration Faults During Start-Up or Operation
 
Recoverable configuration faults are also indicated by the "Status" LED, but by different 
flashing patterns. 
 
The various configuration faults and their corresponding LED flashing patterns are 
described below. 
Note: Shut down power before corrective action. After modification of configuration the 
set-up procedure as described in the next chapter is required. 
 
[In the table below, Logic Module, Robot Module, and Additional Safe Area Module are 
Input Modules whose rotary switches are set for the corresponding function.] 
 
Fault Indication
Corrective
Action
Logic Module and Muting 
Module installed in system 
"Status" LED flashes 6 x
Modify modules 
configuration 
Logic Module and Robot 
Module installed in system 
"Status" LED flashes 6 x
Modify modules 
configuration 
Logic Module and 
Additional Safe Area 
Module installed in system 
"Status" LED flashes 6 x
Modify modules 
configuration 
More than one Robot 
Module installed in system 
"Status" LED flashes 6 x
Modify modules 
configuration 
More than one Additional 
Safe Area Module installed 
in system 
"Status" LED flashes 6 x
Modify modules 
configuration 
More than one Muting 
Module installed in system 
"Status" LED flashes 6 x
Modify modules 
configuration 
Additional Safe Area 
Module installed without 
Robot Module 
"Status" LED flashes 6 x
Modify modules 
configuration 
Muting Module installed 
without Robot Module 
"Status" LED flashes 6 x
Modify modules 
configuration 
Robot Module installed 
without Group 1 or 2 
Output Module 
"Status" LED flashes 6 x
Modify modules 
configuration 
Logic Module installed 
without Group 1 Output 
Module 
"Status" LED flashes 6 x
Modify modules 
configuration 
Terminals Y40, Y41, Y42, 
S34 wrongly connected. 
"Status" LED flashes 7 x
Connect these terminals 
only as follows: 
Jumper: Y40 - Y41 
Jumper: Y40 - Y42 
Jumper: Y40 - S34 
At least one Input Module 
has difference in redundant 
rotary switches settings. 
"Status" LED continuously 
lighted, red. 
All input LEDs of the 
offending Input Module 
flash, red 
Adjust rotary switch 
settings: both sets must 
match