3.1.2 MSR300 Safety Relay Functions

MSR300 Systems can be used for various safety relay functions outlined below, when
appropriately configured for the respective function.
Simultaneity monitoring (sometimes referred to as synchronization monitoring or
coincidence gating) is often necessary for many of these safety applications. This means
that 2 (sometimes even 3) input contacts must be closed (or reset) simultaneously to
clear this set of inputs (simultaneity between all channels of one input). For these
applications, the allowable time window is 3 seconds. Another common application that
involves simultaneity monitoring (0.5 seconds window) is two-hand safety control.
(simultaneity activation of both inputs of one module).

3.1.2.1

One-Channel Emergency Stop

• Safety output contacts are opened if the input loop is open.

• Stop category: 0.

• Short-circuiting of the input loop to electrical ground or 24V will be detected.

3.1.2.2 Two-Channel

Emergency

Stop

• Safety output contacts are opened if at least one input loop is open.

• Stop category: 0.

• Short-circuiting of the input loop to electrical ground or 24V will be detected.

• Cross loops will be detected.

• Suitable for use with safety mats.

• Can be configured for simultaneity detection: 3 seconds limit.

3.1.2.3

Three-Channel Emergency Stop

• Safety output contacts are opened if at least one input loop is open.

• Stop category: 0.

• Short-circuiting of the input loop to electrical ground or 24V will be detected.

• Cross loops will be detected.

• Can be configured for simultaneity detection: 3 seconds limit.

3.1.2.4

Two-Channel Safety Gates

• Safety output contacts are opened if the N/O input is closed or the N/C input is

open

• Stop category: 0.

• Short-circuiting of the input loop to electrical ground or 24V will be detected.

• Cross loops will be detected.

• Can be configured for simultaneity detection: 3 seconds limit.

• Can be configured to execute a start-up test of the input loops.

3.1.2.5 Two-Channel

Light

Curtain

• Safety output contacts are opened if one or more inputs have has no signal.

• Stop category: 0.