Read Multiple Registers (0x03)

Query:

Fieldname

Example

Slave Address

0x01

Function Code

0x03

Start Address (High byte)

0x00

Start Address (Low byte)

0x02

Number of registers (High byte)

0x00

Number of registers (Low byte)

0x02

CRC (High byte)

0x65

CRC (Low byte)

0xCB


Response:

Fieldname

Example

Slave Address

0x01

Function Code

0x03

Byte Count

0x04

Data (High byte)

0x1F

Data (Low byte)

0x70

Data (High Byte)

0xC0

Data (Low Byte)

0x04

CRC (High byte)

0xAD

CRC (Low byte)

0xFF


Error Response:

Fieldname
Slave Address

0x01

Function Code

0x83

Exception Code

(See supported exception codes)

CRC (High byte)

0x..

CRC (Low byte)

0x..