Publication 1761-UM006E-EN-P - August 2005

9-4 Troubleshooting

Table 9.5 Series C LED Indicators

LED

Description

Color

State

Indicates

POWER

module power

green

on

The module is powered.

off

The module does not have power.

TX/RX

RS-232 data
transmission
indicator

green

flashing

Data is being transmitted or received over the RS-232 port.

off

No RS-232 traffic.

10

10-Base-T
Ethernet link
status and data
transmission
indicator

off

No link or continuous data activity on 10MB Ethernet.

amber

on

10-Base-T half-duplex: Link is good, but there is no data activity.

flashing

10-Base-T half-duplex: Link is good with sporadic data activity.

(1)

green

on

10-Base-T full-duplex: Link is good, but there is no data activity.

flashing

10-Base-T full-duplex: Link is good with sporadic data activity.

(1)

100

100-Base-T
Ethernet link
status and data
transmission
indicator

off

No link or continuous data activity on 100MB Ethernet.

amber

on

100-Base-T half-duplex: Link is good, but there is no data activity.

flashing

100-Base-T half-duplex: Link is good with sporadic data activity.

(1)

green

on

100-Base-T full-duplex: Link is good, but there is no data activity.

flashing

100-Base-T full-duplex: Link is good with sporadic data activity.

(1)

FAULT

fault condition
indicator

red

on

lit when a fault condition is present, possible causes

• Duplicated IP address on network

• Network controller error

flashing

one of the following:

• faulty network connection at power up

• ENI/ENIW does not have a valid IP address

• No BootP/DHCP response

off

Hardware is functioning normally

(1) Network activity is not necessarily to/from the ENI/ENIW.