Rockwell Automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) User Manual User Manual

Page 125

Advertising
background image

Publication 1761-UM006E-EN-P - August 2005

Troubleshooting 9-5

Table 9.6 Series D LED Indicators

LED

Description

Color

State

Indicates

POWER

module power

green

on

The module is powered.

off

The module does not have power.

RS-232
TX/RX

RS-232 data
transmission
indicator

green

flashing

Data is being transmitted or received over the RS-232 port.

off

No RS-232 traffic.

LINK

Ethernet
activity status
and 10-Base-T
or 100-Base-T
indicator

off

No link or continuous data activity on 10MB Ethernet.

amber

on

10-Base-T link is good.

green

on

100-Base-T link is good.

TX/RX

Ethernet
activity status
and half-duplex
or full-duplex
indicator

Off

No activity.

amber

flashing

Half-duplex data activity.

(1)

green

flashing

Full-duplex data activity.

(1)

FAULT

fault condition
indicator

red

on

lit when a fault condition is present, possible causes

• Duplicated IP address on network

• Network controller error

flashing

one of the following:

• faulty network connection at power up

• ENI/ENIW does not have a saved IP address (uses default IP address

192.168.1.254)

• No BootP/DHCP response

off

Hardware is functioning normally.

(1) Any Ethernet network activity; not necessarily to/from the ENI/ENIW.

Advertising