The ENI and ENIW provide EtherNet/IP connectivity for RS-232
devices that use DF1 full-duplex protocol. DF1 full-duplex is an open,
point-to-point protocol used in any Allen-Bradley controller with an
RS-232 port, and in many other devices. DF1 full-duplex supports up
to 255 node addresses. The ENI and ENIW use these node addresses
for different functions.

The ENI and ENIW use a memory (node) map to provide access to
the different functions you can perform. Each function uses a different
group of node addresses. The following table illustrates the ENI and
ENIW functions by groups of node numbers:

General Ethernet
Information

Each Ethernet device requires a unique IP address. If your Ethernet
network is isolated from the company-wide network, any valid IP
address may be used. If your Ethernet hub is connected to a larger
Ethernet network, contact your System Administrator for unique IP
addresses.

RSLinx/RSWho
Connectivity Example
Using ENI/ENIW Interface

For this example, the following IP addresses will be assigned to the
various Ethernet devices on our network:

ENI and ENIW
Function

Node Group

Node Function

Valid Data Type

For More
Information

Message Routing

Node 100 to 149

Configure Route Address

Integer

see chapter 5

Node 0 to 49

Route DF1 MSG to IP at Configured Route
Address

Integer

see chapter 5

Email

Node 150 to 199

Configure SMTP email address

String

see chapter 6

Node 50 to 99

Send email message to configured SMTP
email address

String

see chapter 6

Web Data

Node 200 to 204

ENIW Web page data

String, integer, or
floating point

see chapter 7

ENI and ENIW
Configuration

Node 241 to 254

ENI and ENIW Configuration Registers

Integer or String
depending on parameter

see chapter 4

Table 3.1 Example Network IP Addresses

IP Address

ENI or ENIW Series

Device

131.200.50.92

SLC 5/05 controller

131.200.50.93

1756-ENBT

131.200.50.94

Series A ENI

1761-NET-ENI #2 (1769-20 or 1769-L3x
CompactLogix controller)

131.200.50.95

Series A ENI or B/C/D
(ENI or ENIW)

1761-NET-ENI #1 (computer COMM port)