Rockwell Automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) User Manual User Manual

Page 56

Advertising
background image

Publication 1761-UM006E-EN-P - August 2005

4-16 ENI/ENIW Configuration (Nodes 241 to 254)

instruction to the ENI/ENIW (or by using the ENI/ENIW Configuration
Utility).

1. Configure a 485CIF/PLC2 write message in the Allen-Bradley

controller.

2. Set the destination (target) node to 250. Using node address 250

directs this message to the TCP/IP configuration function.

3. The local integer file must be set up for at least 4 integer

locations. The first 4 words define the IP address and are
required. All remaining variables are optional.

The table below describes the TCP/IP functions that can be
configured. The sections following the table describe the functions in
more detail.

IMPORTANT

To configure TCP/IP parameters in this manner,
BOOTP and DHCP must be disabled.

Only PLC2 type or 485CIF write messages can
be used to configure the ENI/ENIW, node 250.

Table 4.4 TCP/IP Configuration Parameters

Function

(1)

(1) The IP address must be configured. All other functions are optional.

Data
Type

Length

Notes

IP Address

Integer

4 words

Format aaa.bbb.ccc.ddd (decimal). The
ENI/ENIW verifies the first/highest octet of any
IP as follows:

• The first octet is between 1 and 223 and

not equal to 127.

• The first two octets are not equal to

169.254 or 169.255.

• The first octet is 0, and the entire IP is

0.0.0.0.

Otherwise the IP address is treated as an error.

For example, 0.168.0.75 is an error, or 127.0.0.0
is an error
.

Subnet Mask

Integer

4 words

If not sent, the default mask is derived from the
class of the IP address as shown in Table 4.5.

Gateway

Integer

4 words

Only needed if a Gateway is present on the
Subnet. The default is 000.000.000.000.

Security Mask 1

Integer

8 words

If not present, the default is no security mask
000.000.000.000.

Security Mask 2

Advertising
This manual is related to the following products: