Publication 1761-UM006E-EN-P - August 2005

Installation and Wiring 2-7

RS-232 Port Connections

RS-232 Connector

RS-232 Cables

Port 2 of the ENI/ENIW is an 8-pin mini-DIN RS-232 port that provides
connection to DF1 compatible RS-232 devices. The table below
describes the RS-232 compatible cables.

See page 2-2 for the list of cables that can be used in a hazardous
environment.

Table 2.1 RS-232 Connector Pin Assignments

Pin

Port 2

1

24V dc

2

ground (GND)

3

no connection

4

ENI/ENIW input data, RxD

5

no connection

6

no connection

7

ENI/ENIW output data, TxD

8

ground (GND)

ENI/ENIW Connected to:

Catalog Number

Use Cable

MicroLogix 1000, 1100, 1200, and
1500, Channel 0 (all series)

1761-CBL-AM00
1761-CBL-HM02

Mini DIN to Mini DIN
45 cm (17.7 in)
2m (6.5 ft.)

SLC 5/03, SLC 5/04, or
SLC 5/05, Channel 0
MicroLogix 1500 LRP, Channel 1
CompactLogix, FlexLogix, or
ControlLogix serial ports

1761-CBL-AP00
1761-CBL-PM02

Mini DIN to D-Shell
45 cm (17.7 in)
2m (6.5 ft.)

8-pin mini-DIN

4

2

1

5

8

7

6

3