Publication 1761-UM006E-EN-P - August 2005

ENI/ENIW Configuration (Nodes 241 to 254) 4-3

If a Configuration Security Mask is set to

192.168.255.76

all source IP Addresses that equal

192.168.xxx.76

will be accepted.

RS-232 Baud Rate, TCP/IP Parameters, BOOTP/DHCP, and Ethernet
Speed/Duplex Options

Use the ENI/ENIW IP Addr tab to set the following:

• ENI Series – Select A, B/C or D, depending on which series

ENI/ENIW you are configuring.

• 232 Baud Rate – Select a baud rate or choose Autobaud. See

page 4-14 for more information.

• TCP/IP Parameters – See page 4-15 for more information on

valid addresses.

(1)

• Obtain via BOOTP – At power-up, if the ENI/ENIW does not

already have a saved IP address, it transmits a BOOTP request. If
a BOOTP response is received, this IP address is saved for all
subsequent power cycles. If a BOOTP response is not received,
then the fault LED continues to flash and no further Ethernet
communication takes place (series A, B, and C). For series D
only, in this situation, Ethernet configuration can be
accomplished using the default IP address or 192.168.1.254.

• Other BOOTP/DHCP Options – See the following section on

series B and higher options and also see Table 4.3 on page 4-15
for details on the settings.

(1) Entering leading zeros in the octets of the IP address will not convert the decimal address to a octal value.

TIP

If you want to obtain the TCP/IP information
via BOOTP, you must do that separately from
the ENI/ENIW Configuration Utility. See
Appendix B.