C-2 1761-NET-ENI/ENIW Performance Considerations

Data Throughput

In tests performed using the RSLinx OPC Test Client, the ENI/ENIW
(series D) was connected to a MicroLogix 1500 with channel 0 set to
38.4 kbaud. The Ethernet port was connected to the computer
through a 10/100 Mbps switch.

The maximum number of minimum-sized packets per second that can
be transmitted through the ENI/ENIW (series D) at 100 Mbps to a
MicroLogix 1500 at 38.4 kbaud is 94 (94 words/second).

The maximum number of 100-word packets per second that can be
transmitted through the ENI/ENIW (series D) at 100 Mbps to a
MicroLogix 1500 at 38.4 kbaud is 15 (1500 words/second).

Number of Packets

Packet Size (Words)

Packet Rate (packet/s)

1

1

31

2

1

62

3

1

75

4

1

86

5

1

88

6

1

94

7

1

94

Number of Packets

Packet Size (Words)

Packet Rate (packet/s)

1

100

7

2

100

14

3

100

15

4

100

15