ENI/ENIW Configuration (Nodes 241 to 254) 4-7

1. Open the ENI/ENIW Configuration Utility.

2. On the Utility Settings tab, select the appropriate COM port and

baud rate.

• COM Port – The PC’s RS-232 port that the communications

cable is plugged into.

• Baud Rate – Set the baud rate to match the baud rate

configured for the ENI/ENIW. If you’re not sure which baud
rate the ENI/ENIW is configured for, try the available baud
rates listed in Table 4.2, starting with 38,400 and then 19,200.
These are the most commonly used baud rates.

3. Click the (Load From) ENI button.

The configuration is uploaded from the RS-232 com port.

The ENI/ENIW Configuration Utility may now be used for all
configuration operations over RS-232.