Rockwell Automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) User Manual User Manual

Page 66

Advertising
background image

Publication 1761-UM006E-EN-P - August 2005

4-26 ENI/ENIW Configuration (Nodes 241 to 254)

Table 4.10 Message Instruction Variables for Configuring ENI/ENIW String
Parameters

Variable

Setting

This Controller Parameters:

Communication Command For the ENI/ENIW configuration, this must be set to:

• 485CIF for MicroLogix and SLC

• a PLC2 Unprotected Write command for CompactLogix

and PLC-5

Data Table Address

In this example we are using string file 25, element 0 (ST25:0)

Size in Elements

For all ENI/ENIW parameters that require a string
configuration, always set this to 1.

Channel

The RS-232 communication channel that is connected to the
ENI/ENIW, typically 0 or 1.

Target Device Parameters:

Message Timeout

Leave this value at the default.

Data Table Offset

Always 0.

Local Node Addr (dec).

This is the destination node address, in this example it is 249.

Local/Remote

Always Local.