Rockwell Automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) User Manual User Manual
Page 39
Advertising

Publication 1761-UM006E-EN-P - August 2005
Operation 3-9
RSLinx Configuration
1. Open RSLinx.
2. Open the configure drivers dialog box.
3. Select RS-232 DF1 devices. Click Add New.
4. Configure AB_DF1-1 driver to match the example below.
5. Click OK when the AB_DF1-1 driver is configured.
TIP
The 1770-KF3/1747-KE device type only allows you
to address nodes 0 to 31 (decimal). In order to
address nodes 32 to 49, you must select the
1770-KF2/1785-KE device type and convert the octal
addresses to decimal (40
8
= 32
10
. . . 61
8
= 49
10
).