Rockwell Automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) User Manual User Manual

Page 16

Advertising
background image

Publication 1761-UM006E-EN-P - August 2005

1-4 Product Overview

After out-of-box power-up, the most common reason for a flashing
red fault LED is because an IP address has not yet been assigned via
BOOTP. Either set up a BOOTP server to assign an IP address or
modify the ENI/ENIW configuration to use a specific IP address or to
obtain an IP address via a DHCP server.

For more detailed information on LED operation, see Chapter 9,
Troubleshooting.

Table 1.3 Series D Descriptions

LED

Description

Function

Color

RS-232
TX/RX

RS-232 data
transmission indicator

RS-232 port is transmitting or
receiving data

flashing green

no RS-232 traffic

off

POWER

module power

module is powered

green

LINK

Ethernet link status and
10-Base-T or
100-Base-T indicator

No link

off

10-Base-T link

amber

100-Base-T link

green

Ethernet
TX/RX

Ethernet activity status
and Half Duplex or Full
Duplex status

No activity

off

Half Duplex activity

(1)

(1) Any Ethernet network activity; not necessarily to or from the ENI/ENIW.

flashing amber

Full Duplex activity

(1)

flashing green

FAULT

fault condition
indicator

lit when a fault condition is
present

red or flashing
red

FAULT

LINK

Ethernet TX/RX

RS-232 TX/RX

POWER

Series D