Install ControlLogix I/O Modules

Chapter 6

NEMA Clamp

Follow these steps to wire a NEMA clamp.

1.

Strip 8 mm (5/16 in.) maximum length of wire.

2.

Turn the terminal screw counterclockwise.

3.

Insert the stripped end of the wire under the plate on the terminal.

4.

Turn the terminal screw clockwise until the wire is secured.

The open section at the bottom of the RTB is called the strain relief area. The
wiring from the connections can be grouped with a plastic tie.

Spring Clamp

Follow these steps to wire a spring clamp.

1.

Strip 11 mm (7/16 in.) maximum length of wire.

2.

Insert the screwdriver into the outer hole of the RTB to depress the spring-
loaded clamp.

3.

Insert the wire into the open terminal and remove the screwdriver.

Strain Relief Area

40201-M

20860-M

Strain Relief Area