Fast Module Features

Chapter 5

Dedicated Connection for Event Tasks

The 1756-IB16IF input module can initiate an event task over a dedicated
second connection in response to four user-defined input patterns. You can
define these patterns in real time during a control process by using these output
tags:

Event[

x].Mask—Defines which input points trigger the event task.

Event[

x].Value—Defines whether the masked input points must be in the

On or Off state before the event task is triggered.

Each pattern can use any of the module’s 16 input points, as shown in the
examples below.

In example pattern 1, the input module triggers the event task when input points
0…7 are in the On state.

In example pattern 2, the input module triggers the event task when input points
0…7 are in the Off state.

In example pattern 3, the input module triggers the event task when input points
4, 6, 8, and 10 are in the On state.

Table 18 - Example Pattern 1

Output Tag

Bit Position

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Event[x].Mask

1

1

1

1

1

1

1

1

0

0

0

0

0

0

0

0

Event[x].Value

1

1

1

1

1

1

1

1

x

x

x

x

x

x

x

x

Table 19 - Example Pattern 2

Output Tag

Bit Position

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Event[x].Mask

1

1

1

1

1

1

1

1

0

0

0

0

0

0

0

0

Event[x].Value

0

0

0

0

0

0

0

0

x

x

x

x

x

x

x

x

Table 20 - Example Pattern 3

Output Tag

Bit Position

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Event[x].Mask

0

0

0

0

1

0

1

0

1

0

1

0

0

0

0

0

Event[x].Value

x

x

x

x

1

x

1

x

1

x

1

x

x

x

x

x