Chapter 8

Wiring Diagrams

The 1756 digital I/O modules support these features.

Table 30 - 1756 I/O Module Features

Module Type

Features

1756 digital AC input modules

Change of state: Software configurable
Timestamp of inputs: ±200 μs
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756 digital AC output modules

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time
Fault states per point: Hold last state, on or off (off is default)
States in Program mode per point: Hold last state, on or off (off is default)
Fusing:

1756-OA8D, 1756-OA8E: Electronically fused per point
1756-OA16: Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n

H2153.15

All other modules: Not protected. A fused IFM is recommended to protect outputs (see publication

1492-TD008

)

Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756 digital DC input modules

Reverse polarity protection: All modules except 1756-IG16 module
Change of state: Software configurable
Timestamp of inputs:

±100 μs for sequence of events modules

(1)

±200 μs for all other modules

Module keying: Electronic, software configurable
RTB Keying: User-defined mechanical

1756 digital DC output modules

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time
Fault states per point: Hold last state, on or off (off is default)
States in Program mode per point: Hold last state, on or off (off is default)
Fusing:

1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OB16IEF, 1756-OB16IEFS, 1756-OV16E, 1756-OV32E:

Electronically fused per point

All other modules not protected. A fused IFM is recommended to protect outputs. See publication

1492-TD008

.

Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756 digital contact modules

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time
Configurable fault states per point: Hold last state, on or off (off is default)
Configurable states in Program mode per point: Hold last state, on or off (off is default)
Fusing: Not protected. A fused IFM is recommended to protect outputs (See publication

1492-TD008

)

Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

(1) For details, see the ControlLogix Sequence of Events Module Installation Instructions, publication

1756-IN592

, and the ControlLogix Sequence of Events Module User Manual, publication

1756-UM528

.

IMPORTANT

For the latest I/O module specifications, see the 1756 ControlLogix I/O Modules
Technical Specifications, publication

1756-TD002

.