Configurable point-level output states – Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

55

Common Module Features

Chapter 3

Configurable Point-level Output States

Individual outputs can be configured to unique output states if the module goes
into Program mode or Fault mode.

Follow these steps to configure an output state.

1.

On the Module Properties dialog box, click the Configuration tab.

2.

From the Program Mode pull-down menu, choose whether the module’s
output state is On or Off during Program mode:

On

Off

Hold (Retain current output state)

3.

From the Fault Mode pull-down menu, choose whether the module’s
output state during Fault mode:

On

Off

Hold (Retain current output state)

4.

Click OK.

IMPORTANT

Whenever you inhibit an output module, it enters Program mode, and all
outputs change to the state configured for Program mode. For example, if an
output module is configured so that the state of outputs turn Off during
Program mode, whenever that module is inhibited, outputs turn Off.