Choose a Correct Power Supply

Use the chart to determine the power your ControlLogix chassis is using to
prevent an inadequate power supply. We recommend that you use this worksheet
to check the power supply of each ControlLogix chassis used.

Slot
Number

Module
Cat. No.

Current @
5.1V DC (mA)

Power @
5.1V DC (Watts)

Current @
24V DC (mA)

Power @
24V DC (Watts)

Current @
3.3V DC (mA)

Power @
3.3V DC (Watts)

0

x 5.1V =

x 24V =

x 3.3V =

1

x 5.1V =

x 24V =

x 3.3V =

2

x 5.1V =

x 24V =

x 3.3V =

3

x 5.1V =

x 24V =

x 3.3V =

4

x 5.1V =

x 24V =

x 3.3V =

5

x 5.1V =

x 24V =

x 3.3V =

6

x 5.1V =

x 24V =

x 3.3V =

7

x 5.1V =

x 24V =

x 3.3V =

8

x 5.1V =

x 24V =

x 3.3V =

9

x 5.1V =

x 24V =

x 3.3V =

10

x 5.1V =

x 24V =

x 3.3V =

11

x 5.1V =

x 24V =

x 3.3V =

12

x 5.1V =

x 24V =

x 3.3V =

13

x 5.1V =

x 24V =

x 3.3V =

14

x 5.1V =

x 24V =

x 3.3V =

15

x 5.1V =

x 24V =

x 3.3V =

16

x 5.1V =

x 24V =

x 3.3V =

Totals

mA

W (1)

mA

W (2)

mA

W (3)

This number
cannot exceed the
following:
10000 mA for
1756-PA72, 1756-
PB72
13000 mA for
1756-PA75,
1756PB75, 1756-
PC75, 1756-PH75

This number
cannot exceed
2800 mA

This number
cannot exceed
4000 mA

These three wattage values (1, 2, 3), added together, cannot exceed 75 W @ 60 °C (140 °F) for any power supply.