75

Diagnostic Module Features

Chapter 4

Features Specific to
Diagnostic Output Modules

The table below lists features specific to ControlLogix diagnostic digital output
modules.

Field Wiring Options

As with diagnostic input modules, ControlLogix diagnostic output modules
provide isolated or nonisolated wiring options. I/O modules provide point-to-
point, group-to-group, or channel-to-channel wiring isolation.

Your specific application determines what type of isolation is necessary and
which output module to use.

No Load Detection

For each output point, no load detection senses the absence of field wiring or a
missing load from each output point in the Off state only.

The output circuit on a diagnostic output module has a current sensing
optoisolator used in parallel with the output transistor. Current flows through
this sensing circuit only when the output is Off, as shown in the simplified
diagram.

Topic

Page

Field Wiring Options

75

No Load Detection

75

Field-side Output Verification

76

Pulse Test

78

Diagnostic Change of State for Output Modules

79

IMPORTANT

Although some ControlLogix diagnostic I/O modules provide nonisolated,
field-side wiring options, each I/O module maintains internal electrical
isolation between the system side and field side.

Current
Sense

Load

V+

41681

Output
Transistor

Current Flow with
Output Off

Current Flow with

Output On