Appendix B

Tag Definitions

Standard and Diagnostic
Output Module Tags

ControlLogix standard and diagnostic digital output modules have three types of
tags:

• Configuration

—S

tructure of data sent from the controller to the I/O

module upon powerup.

• Input

Structure of data continually sent from the I/O module to the

controller containing the current operational status of the module.

• Output

Structure of data continually sent from the controller to the I/O

module that can modify the module behavior.

IMPORTANT

The table lists all possible standard or diagnostic output module tags. In each
application, the series of tags varies, depending on how the module is
configured.

Table 37 - Standard Output Module Configuration Tags

Name

Data Type

Definition

FaultMode
(1bit per point)

DINT

Fault Mode—Used in conjunction with FaultValue to configure the state of outputs when a communication fault occurs.
See FaultValue.
0 = Use FaultValue (Off or On)
1 = Hold Last State

FaultValue
(1 bit per point)

DINT

Fault Value—Used in conjunction with FaultMode to configure the state of outputs when a communication fault occurs.
See FaultMode.
0 = Off
1 = On

ProgMode
(1 bit per point)

DINT

Program Mode—Used in conjunction with ProgValue to configure the state of outputs when the controller is in Program
mode. See ProgValue.
0 = Use ProgValue (Off or On)
1 = Hold Last State

ProgValue
(1 bit per point)

DINT

Program Value—Used in conjunction with ProgMode to configure the state of outputs when the controller is in Program
mode. See ProgMode.
0 = Off
1 = On

ProgToFaultEn
(1 byte per module)

BOOL

Program to Fault Transition—Diagnostic enables the transition of outputs to FaultMode if a communication failure
occurs in Program mode. Otherwise outputs will remain in Program mode. See ProgMode, ProgValue, FaultMode,
FaultValue.
0 = Outputs stay in Program mode if a communication failure occurs.
1 = Outputs go to FaultMode if a communication failure occurs.