Chapter 2

Digital I/O Operation in the ControlLogix System

Ownership

I/O modules in a ControlLogix system can be owned by an RSLogix™ 5000
controller. An owner-controller fulfills these functions:

Stores configuration data for every module that it owns

Sends I/O modules configuration data to define module behavior and
begin module operation with the control system

Resides in a local or remote chassis in regard to the I/O module’s position

Each ControlLogix I/O module must continuously maintain communication
with its owner-controller to operate normally.

Typically, each module in the system will have only one owner-controller. Input
modules can have more than one owner-controller. Output modules, however,
are limited to a single owner-controller.

For more information about using multiple owner-controllers, see

Configuration

Changes in an Input Module with Multiple Owners on page 35

.

Use RSNetWorx and
RSLogix 5000 Software

The I/O configuration within RSLogix 5000 software generates the
configuration data for each I/O module in the control system, including modules
in a remote chassis. A remote chassis contains the I/O module but not the
module’s owner-controller. A remote chassis can be connected to the controller
via an EtherNet/IP network or a scheduled connection on the
ControlNet network.

Configuration data from RSLogix 5000 software is transferred to the controller
during the program download and subsequently transferred to I/O modules. The
I/O modules in the local or remote chassis are ready to run as soon as the
configuration data has been downloaded. However, to enable scheduled
connections to I/O modules on the ControlNet network, you must schedule the
network by using RSNetWorx™ for ControlNet software.

RSNetWorx software transfers configuration data to I/O modules on a scheduled
ControlNet network and establishes a network update time (NUT) for the
ControlNet network that is compliant with the desired communication options
specified for each module during configuration.

Anytime a controller references a scheduled connection to I/O modules on a
scheduled ControlNet network, you must run RSNetWorx software to configure
the ControlNet network.