Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual

Page 66

Advertising
background image

66

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

Chapter 3

Common Module Features

The following illustration offers an overview of the fault reporting process on
ControlLogix digital output modules

.

Module-fault Word

All modules

Fuse Blown Word

Point Level

Group Level

1756-OA8D

1756-OA16

1756-OA8E

1756-OB16E

1756-OB8EI

1756-OV16E

1756-OB16D

1756-OV32E

1756-OB16IEF

Field Power Loss Word

1756-OA8E only

41457

Bit 31

Bit 0

A blown fuse for any point or group sets the bit for that point or group in the
fuse blown word and also sets the appropriate bits in the module-fault word.

A communications fault sets all bits in the module-fault word. A fuse blown or
field power loss condition sets the appropriate bits in the module-fault word.

A loss of field power from any group sets the bit for that point in the field power
loss word and also sets the appropriate bits in the module-fault word.

Group 0

Group 0

Group 1

1

1

Group 1

1

1