Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

Appendix A

Troubleshoot Your Module

Figure 21 - Input Module Status Indicators by Catalog Number

Status Indicators
for Output Modules

ControlLogix output modules support the status indicators described in

Table 32

below. The available status indicators vary by module catalog number, as

shown in

Figure 22 on page 179

.

AC INPUT

1756-IA8D, 1756-IA16

AC INPUT

1756-IB16, 1756-IB16I,
1756-IC16, 1756-IG16,
1756-IH16I, 1756-IV16

DC INPUT

ST 0 1 2 3 4 5 6 7

FLT 0 1 2 3 4 5 6 7

DIAGNOSTIC

O
K

OK Status
Indicator

I/O Status

Indicator

Fault

Status Indicator

O
K

20945

ST 0 1 2 3 4 5 6 7

FLT 0 1 2 3 4 5 6 7

ST 8 9 10 11 12 13 14 15

FLT 8 9 10 11 12 13 14 15

DIAGNOSTIC

O

K

DC INPUT

1756-IB16D

DC INPUT

1756-IA32, 1756-IV32

ST 0 1 2 3 4 5 6 7

ST 8 9

1 1 1 1 1 1
0 1 2 3 4 5

ST 1 1 1 1 2 2 2 2

ST 6 7 8 9 0 1 2 3

ST 2 2 2 2 2 2 3 3

ST 4 5 6 7 8 9 0 1

O

K

AC INPUT

1756-IA8D, 1756-IA16I,
1756-IM16I, 1756-IN16

O
K

1756-IB16IF

DC INPUT

PEER DEVICE

O
K

0 1 2 3 4 5 6 7

8 9 10 11 12 13 14 15

ST

ST

0 1 2 3 4 5 6 7

8 9 10 11 12 13 14 15

ST

ST

0 1 2 3 4 5 6 7

8 9 10 11 12 13 14 15

ST

ST

Table 32 - Status Indicators for Output Modules

Indicator

Status

Description

OK Status

Steady green

The outputs are actively being controlled by a system processor.

Flashing green

The module has passed internal diagnostics but is not actively controlled
or it is inhibited or controller is in Program mode.
Uninhibit connection, establish connection or transition controller to
Run mode to enable communication to module.

Steady red

The module must be replaced.

Flashing red

Previously established communication has timed out.
Check the controller and chassis communication.

I/O Status

Yellow

The output is On.

Fuse Status

Red

A short overload fault has occurred for a point in this group.
Check the wiring for a short-overload. Also check the Module Properties
dialog box in RSLogix 5000 software and reset the fuse.

Fault Status

Red

The output has encountered a fault.
Check the output point at the controller.

Diagnostic Status

Steady red

The output has encountered a fault.
Check the output point at the controller.

Flashing red

The output is listening for peer inputs and using the inputs to determine
the state of the output point.