Configure ControlLogix Digital I/O Modules

Chapter 7

The tables below describe the communication and connection formats available
for output modules.

Table 28 - Output Module Communication Formats

Communication Format

Data Return

Module

Output Data

The owner-controller sends the module only output data.

1756-OA8, 1756-OA16I, 1756-OB8, 1756-OB8I,

1756-OB16I, 1756-OB16IS

(1)

,

1756-OB32, 1756-OC8, 1756-OG16,
1756-OH8I, 1756-ON8, 1756-OW16I, 1756-OX8I

Scheduled Output Data

The owner-controller sends the module output data and a CST
timestamp value

Rack Optimization

The owner-controller sends all digital output words to the remote
chassis as a single rack image.

Listen Only—Output Data

These formats have the same definition as those above except that
they are Listen-only connections.

Listen Only—Rack Optimization

CST Timestamped Fuse Data—Output Data

The owner-controller sends the module only output data. The
module returns fuse blown status with the value of the system clock
(from its local chassis) when the fuse is either blown or reset.

1756-OA16, 1756-OA8E, 1756-OB16E, 1756-
OB8EI, 1756-OV16E, 1756-OV32E

CST Timestamped Fuse Data—Scheduled Output Data

The owner-controller sends the module output data and a CST
timestamp value. The module returns fuse blown status with the
value of the system clock (from its local chassis) when the fuse is
either blown or reset.

Listen Only - CST Timestamped Fuse Data—Output Data This choice has the same definition as CST timestamped fuse data -

output data except that it is a Listen-only connection.

Full Diagnostics—Output Data

The owner-controller sends the module only output data. The
module returns diagnostic data and a timestamp of diagnostics.

1756-OA8D, 1756-OB16D

Full Diagnostics—Scheduled Output Data

The owner-controller sends the module output data and a CST
timestamp value. The module returns diagnostic data and a
timestamp of diagnostics.

Listen Only—Full Diagnostics—Output Data

This format has the same definition as Full diagnostics - output data
except that it is a Listen-only connection.

Scheduled Output Data per Point

The owner-controller sends the module output data and a CST
timestamp value.

1756-OB16IS only

(1) The 1756-OB16IS module does not support the Rack optimization, Listen only—rack optimization and Scheduled output data communication formats.

Table 29 - Output Module Connection Formats

Connection Format

Output Data

Data Return

Module

Data

Data

The owner-controller sends the module only output data.

1756-OB16IEF, 1756-OB16IEFS

Scheduled Per Module

The owner-controller sends the module output data and a CIP Sync
timestamp value.

1756-OB16IEF

Scheduled Per Point

The owner-controller sends output data and a CIP Sync timestamp
value to points configured for scheduling.

1756-OB16IEFS

Listen Only

None

Establishes a Listen-only connection with no data.

1756-OB16IEF, 1756-OB16IEFS

Peer Input with Data

Data with Peer

Establishes a Listen-only connection to input peer modules.
See the Peer Ownership Application Technique,
publication

1756-AT016

.

1756-OB16IEF