Chapter 5
Fast Module Features
Follow these steps to configure input filter times.
1.
On the Module Properties dialog box, click the Configuration tab.
2.
In the Input Filter Time column, enter Off to On and On to Off input
filter times from 0…30,000 μs and click OK.
3.
Complete the fields as described in the table below and click OK.
Field
Description
Configuration Tag
Enable Filter
To enable filtering for a point, check the corresponding checkbox.
To disable filtering for a point, clear the corresponding checkbox.
Pt[x].FilterEn
Input Filter Time
Off
→
On
Enter an Off to On input filter time from 0…30,000 μs.
FilterOffOn
Input Filter Time
On
→
Off
Enter an On to Off input filter time from 0…30,000 μs.
FilterOnOff