Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual

Page 80

Advertising
background image

80

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

Chapter 4

Diagnostic Module Features

Fault bits in the field-power loss word and open wire word are logically entered
into the module-fault word. Depending on the module type, a bit set in the
module-fault word can mean multiple things, as indicated in the table.

The following illustration provides an overview of the fault reporting process for
digital input modules.

Table 13 - Bits Set in Module-fault Word

Condition

Bits Set

Communications fault

All 32 bits are set to 1, regardless of the module’s density.

Field-power loss

Only the bit affected is set to 1.

Open wire

Module-fault Word

All modules

Field Power Loss Word

1756-IA8D only

Open Wire Word

Bit 31

Bit 0

An open wire condition on any point sets the bit for that point in the open
wire word and also sets the appropriate bit in the module-fault word.

A loss of field power sets the bit for that group in the field-power loss
word and also sets the appropriate bit in the module-fault word.

A communications fault sets all bits in the module-fault word. A field-power loss
or open wire condition sets the appropriate bit in the module -fault word.